Preloader
FLUX ENERGY Authorised Distributors of all Schneider Products
-20%

MVS40N3MF2L – Circuit breaker, EasyPact MVS, 3 Poles, 4000A, 50kA, MF, ET2, fixed, manual

Original price was: NGN7,880,127.94.Current price is: NGN6,304,102.35.
30 people are viewing this right now
MVS40N3MF2L
Brand:

Description

Main
Range EasyPact
Product name MVS40N
Device short name MVS40N
Product or component type Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3P 3d
[In] rated current 4000 A at 40 °C
Network type AC
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code N
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category B
Trip unit name ET2I
Trip unit technology Electronic
Trip unit rating 4000 A
Complementary
Network frequency 50/60 Hz
Control type Manually operated
Mounting mode Fixed
Mounting support Base plate
Rail
Connection position Horizontal
Vertical
Location of connection Rear
[Ui] rated insulation voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 12 kV conforming to IEC 60947-2
Circuit breaker CT rating 4000 A
Breaking capacity 55 kA Icu at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity 55 kA (Ics) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles (with maintenance) conforming to IEC 60947-2
10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Connection pitch 115 mm without spreader
Contact position indicator Yes
[Icm] rated short-circuit making capacity 121 kA (Icm) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2
55 kA (1 s) at 220…440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit protection functions LI
Protection type Overload protection (long time)
Instantaneous short-circuit protection
Fault indication Short-circuit
Overload
Internal fault
Long time pick-up adjustment type Ir Adjustable 9 settings
Long time pick-up adjustment range 0.4…1 x In
Long time delay adjustment type Adjustable 9 settings
[tr] long-time delay adjustment range 0.5…24 s at 6 x Ir
Thermal memory 20 minutes before and after tripping
Instantaneous pick-up adjustment type Ii Adjustable 9 settings
Instantaneous pick-up adjustment range 1.5…10 x Ir
Zone selective interlocking ZSI With
Current sensor rating range 1000/4000 A
Maximum breaking time 25 ms
Maximum closing response time 70 ms
Height 352 mm
Width 422 mm
Depth 297 mm
Net weight 60 kg
Environment
Standards IEC 60947-2
Product certifications CCS
IEC
CCC
GOST
Pollution degree 4 conforming to IEC 60664-1
IP degree of protection IP40
Ambient air temperature for operation -5…70 °C
Ambient air temperature for storage -40…85 °C without control unit
-25…85 °C with control unit
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 42.0 cm
Package 1 Width 35.0 cm
Package 1 Length 50.0 cm
Package 1 Weight 38.0 kg